CSPower OPzS2-2500 Tubular Flooded Battery
p
OPzS2-2500 | |||
Nominal Voltage | 2V(Single Cell) | ||
Design Floating Life @ 25℃ | 20 Years | ||
Nominal Capacity @ 25℃ | 10 hour rate@200.0A,1.8V | 2500Ah | |
Capacity @ 25℃ | 20hour rate (131.3A,1.8V ) | 2626Ah | |
5 hour rate (425A,1.75V ) | 2125Ah | ||
1 hour rate (1580A,1.6V ) | 1580Ah | ||
Internal Resistance | Full Charged Battery@ 25℃ | ≤0.20mΩ | |
Ambient Temperature | Discharge | -15℃~50℃ | |
Charge | 0 ~40 ℃ | ||
Storage | -15 ~50 ℃ | ||
Max.Discharge Current | @ 25℃ 8000A(5s) | ||
Capacity affected by Temperature (10 hour ) | 40℃ | 105% | |
25℃ | 100% | ||
0℃ | 89% | ||
-15℃ | 79% | ||
Self-Discharge@25℃per Month | 2% | ||
Charge (Constant Voltage) @ 25℃ | Standby Use | Initial Charging Current Less than 500.0A Voltage 2.25-2.3V | |
Cycle Use | Initial Charging Current Less than 500.0A Voltage 2.37-2.4V | ||
Dimension (mm*mm*mm) | Length 487±1 * Width 212±1 * Height 770±1 (Total Height 827±1) | ||
Weight (kg) | 189±3% |
CSPower Model |
Voltage (V) |
Capacity (AH) |
Dimension (mm) | Weight (kgs) | ||||
Length | Width | Height | Total Height | No electrolyte | (with electrolyte) | |||
OPzS2-200 | 2 | 200 | 103 | 206 | 355 | 410 | 12.8 | 17.5 |
OPzS2-250 | 2 | 250 | 124 | 206 | 355 | 410 | 15.1 | 20.5 |
OPzS2-300 | 2 | 300 | 145 | 206 | 355 | 410 | 17.5 | 24 |
OPzS2-350 | 2 | 350 | 124 | 206 | 471 | 526 | 19.8 | 27 |
OPzS2-420 | 2 | 420 | 145 | 206 | 471 | 526 | 23 | 32 |
OPzS2-500 | 2 | 500 | 166 | 206 | 471 | 526 | 26.2 | 38 |
OPzS2-600 | 2 | 600 | 145 | 206 | 646 | 701 | 32.6 | 47 |
OPzS2-800 | 2 | 800 | 191 | 210 | 646 | 701 | 45 | 64 |
OPzS2-1000 | 2 | 1000 | 233 | 210 | 646 | 701 | 54 | 78 |
OPzS2-1200 | 2 | 1200 | 275 | 210 | 646 | 701 | 63.6 | 92 |
OPzS2-1500 | 2 | 1500 | 275 | 210 | 773 | 828 | 81.7 | 112 |
OPzS2-2000 | 2 | 2000 | 399 | 210 | 773 | 828 | 119.5 | 150 |
OPzS2-2500 | 2 | 2500 | 487 | 212 | 771 | 826 | 152 | 204 |
OPzS2-3000 | 2 | 3000 | 576 | 212 | 772 | 806 | 170 | 230 |
Products will be improved without notice, please contact sales for specification in kind prevail. |